Trotec 1510002050 TFV 900 Centrifugal Fan
Description
The optimal solution for all application areas where air transport takes place over long distances.
- Proper ventilation is not only important for a pleasant working atmosphere, but is also absolutely necessary in many areas for occupational safety reasons and due to official regulations.
- By ventilating rooms, harmful substances such as paint or
- Paint fumes, welding fumes, dust particles, carbon monoxide, nitrogen oxide, carbon dioxide, and water vapor are removed.
- The TFV 900 high-pressure centrifugal fan is well-equipped for such tasks, as it can handle high back pressures of up to 33,600 m³/h even over long distances. transports air and is extremely stable for harsh practical environments.
- Because this fan draws in air axially and blows it out radially, it is not only impervious to heavily polluted air with a high dust content, but also ensures high, stable characteristics.
- In addition to the standard version, the TFV 900 fan is also available as an optional rental version.
Here are some practical advantages of the TFV 900 at a glance:
- Particularly robust device with high transport capacity
- Splash-proof design (IP55)
- Also suitable for use in very dusty rooms
- Fan motor is located outside the main airflow
- Can be connected to both inlet and exhaust ducts
- stable characteristic curve regions and continuously high pressure
Here is an overview of the technical data of the TFV 900:
- Free-blowing air volume: 33,600 m³/h
- Air outlet velocity: 34 m/s (122.4 km/h)
- Fans settings: 1
- Max
- Air pressure*: 1,900 Pa
- Max
- Conveyor belt temperature: 80 °C
- Ambient conditions: -20 °C to 40 °C
- Connection voltage: 400 V / 50 Hz (36 A)
- Power connection: CEE 32 A
- Power consumption: 18.5 kW
- Suction connection: accessories (ø 630 mm)
- Discharge nozzle: series (ø 630 mm)
- Noise level (distance 1.5 m): 82 dB (A)
- Housing: steel, powder-coated, 2K paint
- Dimensions (with frame): 1950 x 1900 x 2200 mm
- Weight: 450 kg
Technical specifications
- max. air volume stage - free discharge [m³/h] 33,600
- Air volume at air pressure
m³/h 25,000
Pa 1,900 - Exhaust/suction air flow
- Air outlet velocity m/s34 / km/h 122.4
- Fan speed 1
- Air pressure stage max. [Pa] 2,150
- max. transport medium temperature [°C] 80
- Environmental conditions
- Temperature range min. [°C] -20
- max. temperature range [°C] 40
- Protection feature IP protection class 55
- Mains connection 400 V/50 Hz
- Power consumption [kW] 18.5
- Recommended protection [A / motor protection switch] 32
- Nominal current consumption [A] 39
- Connection plug CEE 63 A
- Intake manifold [mm] 630
- Discharge connection [mm] 630
- Sound levels at 1 m[dB(A)]: 82
- Sound levels at 3 m [dB(A)]: 76
- Length (excluding packaging) [mm]: 1,680
- Width (excluding packaging) [mm]: 1,810
- Height (excluding packaging) [mm]: 1,680
- Weight (excluding packaging) [kg]: 450
Scope of delivery
- TFV 900 Centrifugal fan
Comment